The FTV-C type pneumatic furnace flame monitoring device takes the rod-less cylinder imported from Japan as the power source, and controls the advance and retreat of the cylinder through the electromagnetic reversing valve in the air control cabinet, so that the operator can control the advance and retreat of the optical image transmission mechanism in the central control room or on-site control cabinet. In addition to air-cooled protection and over-temperature protection, the device adds a power-off protection function, I .e. the air control cabinet is equipped with an air storage tank to ensure that the air cylinder can drive the optical image transmission mechanism to automatically enter and exit the furnace under the condition of air-off and power-off. FTV-C type pneumatic furnace flame monitoring device has the advantages of adjustable advance and retreat speed, stable operation, safety and reliability, low failure rate, small maintenance, etc., especially suitable for explosion-proof site.
Main technical parameters
Observation field of view: 50 °, 90 °, 105 °, 120 °;
Lens angle: 0 ° (direct view), 45 °, 60 °;
Working environment of protective cover:-40 ℃ ~ 70 ℃;
Heat-resistant temperature of lens: ≤ 2000 ℃;
Parameters of air source required by the device:
Wind pressure of wind source ≥ 0.3Mpa;
Wind source flow ≥ 0.3m3/min;
Air temperature ≤ 40 ℃, dust particle size ≤ 10 μm;
Oil content ≤ 10 mg/m3;
Working power supply: AC 220V, 50HZ, 300W;
Way of advance and retreat: pneumatic advance and retreat;
Installation method: welding;
Automatic exit conditions;
When the wind pressure at the protection wind inlet of the periscinent tube is lower than 0.04MPa, the timage transmission system automatically exits the work site;
When the temperature in the protective cover is higher than 70 ℃, the image transmission system automatically exits the work site;
When the system is powered off; the image transmission system automatically exits the work site;
Weight of the whole machine: 48kg (on-site probe part).
Product Selection Table
| FTV | Product Number | Number Description | Content | ||||||
| movement mechanism | -A | Electric | It is suitable for the monitoring of coal, gas and various direct fuel combustion industrial furnaces in petrochemical, electric power and metallurgical industries. | ||||||
| -C | Pneumatic type | ||||||||
| -H | Manual | ||||||||
| -G | Fixed | ||||||||
| signal transmission | L | optical cable transmission | Suitable for working conditions with long signal transmission distance and strong signal interference (Transmission distance ≥ 250m). |
||||||
| C | Cable transmission | Suitable for appropriate signal transmission distance and weak signal interference conditions (Transmission distance <250m). |
|||||||
| Air cooling protection | I | Instrument air source | It is applicable to the working condition with instrument air source on site. | ||||||
| II | Vortex air pump air source | It is applicable to the working condition without instrument air source on site. | |||||||
| III | Low pressure air source | It is applicable to the working condition with low pressure wind source on site. | |||||||
| "-" (other function code) | |||||||||
| Function | R | 330 ° electric circumferential rotation | It can comprehensively, timely and intuitively grasp the various working conditions in the furnace, and has a larger monitoring range, especially suitable for various heating furnaces in the petrochemical industry and the monitoring of boilers in the biological power generation industry. | ||||||
| T | furnace temperature measurement | The combination of infrared thermal imaging technology and computer image digital processing technology can measure the real temperature of each target point or designated area in the whole monitoring field of view in the whole furnace in real time. It is especially suitable for all kinds of industrial furnaces in petrochemical industry. | |||||||
| D | intelligent control | Using computer image processing technology for further analysis and processing of surveillance images, so as to achieve fire alarm, automatic compression and storage of images, automatic calibration of flame center, temperature field display and other intelligent control. It is especially suitable for working conditions with strict requirements for intelligent control. | |||||||
| Ex | Explosion-proof | Suitable for petrochemical and power industry for explosion-proof environment The use of demand. Explosion-proof rating: Ex-dIIBT4 Gb/Ex-dIICT4 Gb/Ex-dIICT6 Gb |
|||||||
Selection example
FTV-ACI-TREx
Electric furnace flame monitoring device
Signal transmission: cable transmission, air cooling protection: instrument air source, with 330 ° electric circumferential rotation function, with furnace temperature measurement function, with explosion-proof function